#1. The minimum uniformly distributed live load (UDL) for the stairs serving dwelling unit in a House
#2. A home is being designed for year round residence in Atikokan and utilizes wall sheathing with an air leakage characteristic of 0.09 L/(s×m2) at 75Pa and water vapour permeance of 50 ng/(Pa×s×m2). What is the value of the Ratio of Outboard to Inboard Thermal Resistance given for this location and material condition?
#3. In a building serving a Group D occupancy only, a third storey window located in an exit stair extends to 1000 mm above the finish floor. That window must be;
#4. Waferboard or OSB subflooring must be installed with the direction of face orientation:
#5. Asphalt-coated or asphalt-impregnated fibreboard conforming to CAN/ULC-S706, “Wood Fibre Thermal Insulation for Buildings”, is permitted to be used as a roof sheathing over supports spaced not more than 406 mm o.c., the fiberboard to be
#6. The maximum roof slope for asphalt base (without gravel) of Built-up Roofing is
#7. A house is to be constructed in Hamilton below escarpment and east of Highway 403. The building area is 8 m by 12 m. The specified design snow load for roof framing is:
#8. What is the minimum thickness for hardboard interior finish panels placed directly on studs at 406 mm o.c.?
#9. The minimum thickness of panel-type underlay is
#10. Loadbearing elements in a two storey building of masonry construction are required to have earthquake reinforcement described in Subsection 9.20.15. if the seismic spectral acceleration
#11. In a dwelling unit, hot and cold water must be provided to the following fixtures;
#12. A three way switch is requied at the head and bottom of a stair from the first to second level in a side split house if stairshave
#13. In a house, a guard serving exit stairwell opening between the ground floor and second floor shall be not less than:
#14. The spout on a drinking fountain located in a Barrier-Free path of travel is to be located not more than:
#15. In a steel storage building, a mezzanine that supports mechanical equipment at the back of the building and to which access is provided for maintenance purposes only. The height of the guard required around the mezzanine is:
#16. An air-supported structure occupied by the public must be separated from other structures on the same property by a minimum of;
#17. The minimum compressive strength for concrete used for concrete slabs-on-ground is;
#18. What is the minimum metal thickness of steel studs exclusive of any coatings in an interior non-loadbearing wall with no required fire-resistance rating?
#19. When you design a cavity wall, which of the following parameter will NOT affect the lateral support on top of the wall?
#20. Collar ties may be assumed to provide intermediate support to roof rafters if the roof slope is:
#21. A sheathing membrane that forms part of the second plane of protection for an exterior wall must comply to:
#22. In a loadbearing flat ICF wall, a lintel must also be reinforced for shear with stirrups at openings when the opening is:
#23. A home being constructed in Windsor, Ontario has been changed to include an addition of an indoor swimming pool. The wall assemblies of the swimming pool incorporate materials with a water permeance of less than 60 ng/(Pa×s×m²). High moisture generation will occur and therefore the wall assemblies;?
#24. Consider a dwelling unit where a guard is installed while it is not required by Article 9.8.8.1. The openings through the said guard, which is not required by Article 9.8.8.1., must be of a size that will:
#25. If a streel column that is required to have a fire-resistance rating of not less than 2h. (member demotion: B=164mm. H = 258 mm, mass = 32.8kg/m) Using Section 2.6.1 of Supplementary Standard SB-2, the minimum thickness of type X gypsum wallboard protected protection to be:
#26. Vertically applied metal siding may only be fastened:
#27. A required smoke alarm in a dwelling unit must be installed:
#28. Which one of the following is not an acceptable method for supporting an assembly which required to have a fire-resistance ratings of not less than 45min?
#29. A window is located in an exterior wall of a building adjacent to an enclosed exit stair which also has windows in its exterior wall at every landing level. This particular window is 2 500 mm above the landing and 2 500 mm away from the stair;
#30. Wall assembly, with wood studs @ 406 mm o/c in a single row, using two layers of 15.9 mm Type X gypsum board on each side, with the loadbearing wall FRR 1.5h, nonloadbearing wall FRR 2h. STC 38. The proper wall number in SB-3 is:
#31. The maximum force permitted to open an interior exit door in a Barrier-Free path of travel is;
#32. A guard is required to be installed in a motel to protect guests on second floor. What is the required specified load?
#33. The minimum average level of illumination ina Barrier-Free path of travel is set at:
#34. A barn is being designed which will fall within the area limitations of Part 9. The structural members for this building must be designed
#35. The rear sliding door in a house on the main floor level, the finished floor on one side of the floor is 750mm above the out side ground level on the other side of the sliding door, the door shall be:
#36. In an open floor area, the travel distance to an exit is measured:
#37. 1. A summer cottage will be located in Bancroft, Ontario. The long dimension of low permeable 12.5 mm thick wall sheathing will be applied perpendicular to the wall framing. What installation requirement will insure venting of the framing space and exemption from the requirements of Sentence 9.25.5.1.(1)?
#38. Where the exterior walls of an exit intersect the exterior walls of a building wired glass in steel frames or glass block is required for either the building windows or the exit enclosure windows, where the walls meet at an angle
#39. What is the minimum required number of water closets for a group F, Division 2 occupancy located in a one (1) storey, 600m2 building. The Group F, Division 2 occupancy is located in a suite that is 400m2 in area with occupant load of 18 persons in the suite.
#40. A self-service storage building has an occupant load of 50. How many water closets and lavatories are required?
#41. A Barrier-Free corridor is less than 1 600 mm wide throughout it's length, then widened areas must be provided every 30 m max. These widened areas are;
#42. The minimum length of nails used to fasten 7.9 mm thick wood strip flooring is;
#43. What is the maximum number of dwelling units permitted within a self-service storage building?
#44. The maximum height for a handrail on a ramp serving a Group C occupancy is
#45. Plywood roof sheathing on a 45 degree peak roof with rafters are spaces at 610 mm o.c., the minimum thickness of roof sheathing to be:
#46. Automatic hand dryers for a lavatory in a Barrier-Free washroom are to be located;
#47. An enclosure used for the storage or parking of motor vehicles is considered a carport if it has
#48. In a House the maximum temperature for hot water supply to fixtures other than dishwashers and clothes washers is
#49. A window in a waiting area in a third storey doctor's office extends from the finish floor to the finished ceiling. That window must
#50. A manufactured building falls under the parameters of Section 9.39 if compile with:
#51. The roof framing supported on the top of an ICF wall must be fixed to a top plate which is anchored to the wall with anchor bolts:
#52. A non sprinklered floor area is divided into 2 zones. The occupancy on the floor area is Group D. What is the maximum travel distance from the most remote point in one zone to the door leading into the other zone?
#53. A wall in a building of residential occupancy that is located on a property line shall be constructed as a fire wall except:
#54. The minimum uniformly distributed live load (UDL) for the attic (dry wall ceiling) with access hatch conforming to Subsection 9.19.2. of Division B and having limited accessibility in a House:
#55. What is the minimum thickness of plywood subflooring applied over floor joists spaced at 610 mm o.c. when 19 mm thick hardwood strip flooring is applied over the subfloor?
#56. The suites open into a dead end corridor and have another egress door leading into a exit. What are the specifics for this dead end?
#57. Exterior door assemblies leading to dwelling units from the exterior, an attached garage or other ancillary space or a storage garage need not conform to the “Resistance to Forced Entry” requirements of Articles 9.7.5.2.(3) to 9.7.5.2.(7) provided they conform to:
#58. Consider a two storey single dwelling unit House. The number of required exits is:
#59. A House occupied year-round has a basement and a single storey with cathedral ceilings attached to roof joists. It is equipped with electric baseboard heaters and has two air circulation fans hanging from cathedral ceilings. What is the minimum nominal thermal resistance of ceiling insulation if the House was constructed in Kapuskasing?
#60. The stair case connecting ground floor and basement is:
#61. Except occupancy C, if the combustible content is NOT more than 50kg/m2 or 1200MMJ/m2, this occupancy most likely could be:
#62. A roof, with Code complying asphalt fibreboard sheathing, may support the following type of roofing.
#63. Plywood sheathing, on a flat roof that will be used as a patio with a waterproof vinyl roof and walking deck membrane system that complies with CAN/CGSB-37.54, “Polyvinyl Chloride Roofing and Waterproofing Membrane”, when the roof joists are spaced at 406 mm o.c. must have a minimum thickness of:
#64. The minimum diameter for nails used for the attachment of stucco lath is;
#65. Collar ties must be laterally braced at right angle with a 19 mm × 89 mm brace, if they span more than:
#66. A suite serves a business and personal services occupancy, has an area of 150 m2 and the distance to the nearest egress door is 30 m. How many egress doors are required?
#67. Where an exit door leading directly to the outside is subject to being obstructed by a parked vehicle or storage because of its location?
#68. Tents not occupied by the public are required to be separated from each other by
#69. A building being used as a seasonal recreational building need not to comply with the following previsions as found in part 9 except for the following::
#70. Consider the storage garage of a HOUSE it is detached from the dwelling unit it serves but attached to another storage garage on the adjacent property, the party wall between each section of the storage garage must be constructed as a fire separation with a fire-resistance of not less than:
#71. An exit opens directly into a lobby in an apartment building. The floor is unsprinklered, the lobby is enclosed with a fire separation having a 1hourfire resistance rating. The lobby is 1 m above the ground level and the distance of travel from the exits to the outdoors is 15 m and a suite door opens into a vestibule which in turn opens into the lobby
#72. The manufacturing standards of Tempered or Laminated Safety Glass is:
#73. The exit door serving the House
#74. A roof, with Code complying asphalt fibreboard sheathing, may support the following type of roofing.
#75. A floor joist size is required for a retail store located on the ground floor in a Part 9 building. The span is 4.5 mand the joists are Douglas Fir#1 and 400 mm on centre. Strapping and bridging are provided to the underside of the joists. What is the minimum joist size for this condition?